ProSoft Technology PTQ-104S User Manual

Page 58

Advertising
background image

Module Configuration

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

12TUser Manual

46TIEC 60870-5-104 Server for Quantum

5.3.3 Defining Data to be Retrieved from the PTQ Database.

Your application may need to retrieve 105 words of data from other devices on
the network. These devices have either sent you the data if you are a server, or
you have obtained it for your use if you happen to be a master in your
application. Assuming that the data resides in registers 207 to 312 within the
PTQ modules memory and you wish to place this information in addresses
400208 to 400313 within the Quantum you could use Command Function 2 to
transfer the information.

Because the total amount of data does not exceed 130 words in length, a single
command can be used to transfer the data. This additional entry will be added to
our [Backplane Data Exchange] section and it would look like the third command
below:

The third command states:

Field

Value

Meaning

Command Type

2

The type of operation to perform
2 = Write data from the PTQ to the Quantum

PTQ Address

207

The destination address within the PTQ

Point Type

4

The range of registers to read from the Quantum
4 = 4:x style register

Quantum Address

208

The starting address of the data within the Quantum
This would be Point Type + Quantum Address
Example: 40000 + 207 = 40207

Word Count

105

The number of registers to transfer

Page 58 of 201

ProSoft Technology, Inc.

March 4, 2013