48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

Module Configuration

46TIEC 60870-5-104 Server for Quantum

12TUser Manual

Group Code

Description

0x00010000

Interrogated by group 16 interrogation

0x00020000

Interrogated by general counter request

0x00040000

Interrogated by group 1 counter request

0x00080000

Interrogated by group 2 counter request

0x00100000

Interrogated by group 3 counter request

0x00200000

Interrogated by group 4 counter request

0x40000000

Disable event scanning of this point

0x80000000

Periodic/cyclic data returned from unit

Note 1: Group 3 interrogation also returns the parameter data (ASDU 110 – threshold, low limit

and high limit) for all monitored measured points.

If the highest bit (bit 31) is set, data will be produced by the driver for the
specified point at the rate set for periodic data generation. Bit 30 (0x40000000)
enables scanning of this point for event generation. If the bit is clear and the data
type is set for scanning, events will be generated for the point. If the bit is set,
events will not be generated for the point. This feature can be used to select
which points will generate events for the controlling station and can get rid of
event data that is not important to the application.

5.26 CommonNet Data Map

The Data Map section allows you to copy data between areas in the module's
internal database.

You can copy a maximum of 100 registers per Data Map command, and you can
configure a maximum of 200 separate copy commands.

For example, you can copy data from the error or status tables in upper memory
to internal database registers in the User Data memory area.

You can also rearrange the byte and/or word order during the copy process, for
example, to convert floating-point values to the correct format for a different
protocol.

ProSoft Technology, Inc.

Page 99 of 201