24 [c_se_nc_1 104, 25 group codes, C_se_nc_1 104 – ProSoft Technology PTQ-104S User Manual

Page 98: Group codes

Advertising
background image

Module Configuration

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

12TUser Manual

46TIEC 60870-5-104 Server for Quantum

Each point is one 16-bit word and the DB Address value corresponds to the word
offset in the module memory database. For additional information on how to set
these parameters, see the Reference chapter of this manual.

5.24 [C_SE_NC_1 104]

This section defines the short-float setpoint database. This information is sourced
from the remote Client and is transferred to the database. If the Require Select
parameter is set to one (1) or Y

ES

, a Select command must be received from the

Client before an Execute command from the Client will be processed.

This section takes the following parameters:
 Point #
 DB Address
 Monitor Point #
 Monitor DB Address
 Require Select
Each point is two 16-bit words and the DB Address value corresponds to the
double-word offset in the module memory database. For additional information
on how to set these parameters, see the Reference chapter of this manual.

5.25 Group Codes

One aspect of the point configuration database that leads to confusion is the
group definition field, which assigns each point to one or more interrogation
groups. Use of interrogation groups permits the controlling unit to interface with a
specific set of data. Refer to the IEC 60870-5-104 standard for a full discussion
of interrogation groups. A specific group, Periodic data group, reports data points
on a set frequency. The frequency is set in the Cyclic Data Transmission
parameter in the configuration file. Remember that a point can be assigned to
more than one group.

Group Code

Description

0x00000001

Interrogated by general interrogation (station or global)

0x00000002

Interrogated by group 1 interrogation

0x00000004

Interrogated by group 2 interrogation

0x00000008

Interrogated by group 3 interrogation (See Note 1, below)

0x00000010

Interrogated by group 4 interrogation

0x00000020

Interrogated by group 5 interrogation

0x00000040

Interrogated by group 6 interrogation

0x00000080

Interrogated by group 7 interrogation

0x00000100

Interrogated by group 8 interrogation

0x00000200

Interrogated by group 9 interrogation

0x00000400

Interrogated by group 10 interrogation

0x00000800

Interrogated by group 11 interrogation

0x00001000

Interrogated by group 12 interrogation

0x00002000

Interrogated by group 13 interrogation

0x00004000

Interrogated by group 14 interrogation

0x00008000

Interrogated by group 15 interrogation

Page 98 of 201

ProSoft Technology, Inc.

March 4, 2013