48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

Reference

46TIEC 60870-5-104 Server for Quantum

12TUser Manual

Require Select: This parameter configures the point to require a Select request
before the Operate command.

Control Data Transfer

The control communication typically occurs when the Client sends a command
request to update the module’s command points. The data types addressing are
described in the following table.

Data Type

Data Size

Addressing Type

C_SC_NA

1 bit

Bit

C_DC_NA

2 bits

Bit

C_RC_NA

1 byte

Byte

C_SE_NA

1 word

Word

C_SE_NB

1 word

Word

C_SE_NC

2 words

Word

Some of the command points may be configured to be selected before executed.

Refer to the following parameter to configure the select/operate timeout period.
After the module receives the SELECT operation it will wait for this period of time
for the EXECUTE operation. If the module does not receive an EXECUTE
operation within this period of time it will require another SELECT operation
before the EXECUTE operation.