ProSoft Technology PTQ-104S User Manual

Page 163

Advertising
background image

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

Reference

46TIEC 60870-5-104 Server for Quantum

12TUser Manual

The protocol specification explains that the qualifier value for these commands
should be configured as:

Bits

Value

Description


1 to 6

0

Not Used

1

Threshold Value (Deadband)

2

Smoothing Factor (filter time constant) - Not Supported

3

Low Limit Transmission of Measured Value

4

High Limit Transmission of Measured Value

5..31

Reserved

7

0

No Change

1

Change

8

0

Operation

1

Not in Operation

For the PTQ-104S gateway, the Low Limit and High Limit parameters cannot be
changed by command, because these values are calculated as follows:

Low Limit = (LAST REPORTED VALUE) - Deadband

High Limit = (LAST REPORTED VALUE) + Deadband

These commands must be sent to a specific Information Object Address. The
PTQ-104S gateway associates each Monitor Measured point with a Parameter
point using Parameter Offset entries:

ProSoft Technology, Inc.

Page 163 of 201

March 4, 2013

Advertising