5.6.11 Error Offset

0 to 3980

-1 to disable

This parameter sets the location in the module’s internal database when the
status and error information for the server will be stored. Enter a valid database
address of 0 to 3980 to store the information, or enter -1 to disable.

5.6.12 Command Delay Timer

1000 to 60000 milliseconds

This value is used for time-tag validity verification for the ASDUs listed
below. The received commands will only be accepted if [timestamp + Command
Delay Timer] is greater than the module's own time.
 58: Single command with time tag CP56Time 2a
 59: Double command with time tag CP56Time 2a
 60: Regulating step command with time tag CP56Time 2a
 61: SetPoint command, normalized value with time tag CP56Time 2a
 62: SetPoint command, scaled value with time tag CP56Time 2a
 63: SetPoint command, short floating point with time tag CP56Time 2a
 107: Test command with time tag CP56Time2a
If the value is less than 1000 milliseconds, the module will default to 5000
milliseconds

5.6.13 Maximum ASDU Resp Len

25 to 246

This parameter limits the maximum size of the ASDU portion of a response
message. Most applications will use a value of 246.

5.6.14 Freeze Start Type

D

=

D

AY

,

H

=

H

OUR

,

M

=

M

INUTE

,

N

=

N

OT USED

The Freeze Start Type parameter defines when the module starts sending the
M_IT messages.

5.6.15 Interval for Freeze

0 to 65535

seconds

Freeze Start Type and Interval for Freeze are used if Mode A operation is to be
used for the counter freeze operation. If they are not used, the module will
operate in Mode D.