M_ME_NC

Monitored Measured Normalized Point

Associated Parameter Point

600

2600

601

2601

602

2602

603

2603

...

...

609

2609

In order to send a change of deadband for M_ME_NC Point 600, the Client
would send a command type 110 to point 2600.

Controlling the Generation of Events

Some applications may require that only some points should generate events.
The application will receive current values from points which have not been
configured to generate events only by issuing a poll request, or what the protocol
specification calls an interrogation. Other applications may require that all
configured points generate events.

The PTQ-104S module offers much flexibility for event control. You may control
whether or not events will be generated at three (3) different levels:

1 At the General Application Level (all configured points of all types)
2 At the Data Type Level (all configured points of any data type)
3 At the Individual Point Level (any specific point of any data type)

General (All Points)
The user may control how frequently the module will scan the database for
events using the following configuration parameter: