Iec-870-5-104] section: error offset – ProSoft Technology PTQ-104S User Manual

Page 178

Advertising
background image

Reference

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

12TUser Manual

46TIEC 60870-5-104 Server for Quantum

Word Offset in Block

Data Field(s)

Description

7 to 8

Run Number

This two-word data area contains the text values
for the run number.

9

Reserved

Reserved

[IEC-870-5-104] section: Error Offset

Word Offset in Block

Data Field(s)

Description

0

t0 Timeout

Number of t0 errors recognized by the module

1

t1 Timeout

Number of t1 errors recognized by the module

2

t2 Timeout

Number of t2 errors recognized by the module

3

t3 Timeout

Number of t3 errors recognized by the module

4

Sequence Number
Errors

This word contains the number of sequence
number errors recognized by the module. When the
send sequence number received by the module
does not match the expected sequence number,
the connection is closed and this counter is
incremented

5

Bad Address

This word contains the number of messages
received with a wrong Common ASDU Address
value

6

Bad Length

This word contains the number of messages
received by the host that does not contain a valid
length field

7

Active

1 = Yes, 0 = No.

8

Socket State

This word contains the current socket state as
follows:
-1 = Open Socket
0 = Wait for Connection
1 = Transmit Message if Ready
2 = Receive Packet and process message
3 = Process multiple messages in packet
50 = Send TestFR ACT
51 = Wait for TestFR Con
60 = Send S-Format Message
1000 = Close Socket
1001 = Wait for Socket to Close

9

Socket Open Count This word contains the number of times the socket

listen function was executed

10

Socket Close
Count

This word contains the number of times the an
active close function was executed

11

Socket Connect
Count

This word contains the number of times a
connection was established between with the
remote host unit

Page 178 of 201

ProSoft Technology, Inc.

March 4, 2013