48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

Reference

46TIEC 60870-5-104 Server for Quantum

12TUser Manual

Word Offset in Block

Data Field(s)

Description

4033

Sequence Number
Errors

This word contains the number of sequence
number errors recognized by the module. When the
send sequence number received by the module
does not match the expected sequence number,
the connection is closed and this counter is
incremented

4034

Bad Address

This word contains the number of messages
received with a wrong Common ASDU Address
value

4035

Bad Length

This word contains the number of messages
received by the host that does not contain a valid
length field

4036

Active

!0 = Yes, 0 = No.

4037

Socket State

This word contains the current socket state as
follows:
-1 = Open Socket
0 = Wait for Connection
1 = Transmit Message if Ready
2 = Receive Packet and process message
3 = Process multiple messages in packet
50 = Send TestFR ACT
51 = Wait for TestFR Con
60 = Send S-Format Message
1000 = Close Socket
1001 = Wait for Socket to Close

4038

Socket Open Count This word contains the number of times the socket

listen function was executed

4039

Socket Close
Count

This word contains the number of times the an
active close function was executed

4040

Socket Connect
Count

This word contains the number of times a
connection was established between with the
remote host unit

4041

Event Buffer 0

Event data from MSP free events

4042

Event Buffer 1

Event data from MDP free events

4043

Event Buffer 2

Event data from MST free events

4044

Event Buffer 3

Event data from MMA free events

4045

Event Buffer 4

Event data from MMB free events

4046

Reserved

Reserved

4047

Event Buffer 6

Event data from MIT free events

The module has two parameters to copy parts of the status registers to the
database as follows:

[Backplane Configuration] section: Error Offset

Word Offset in Block

Data Field(s)

Description

0

Scan Count

This status value contains a counter incremented
on each scan of the module's main loop.

1 to 2

Product Name

This two-word data area contains the text values
representing the product name.

3 to 4

Revision

This two-word data area contains the text values
for the revision number.

5 to 6

Op Sys #

This two-word data area contains the text values
for the operating system number.