For example, if you configured the following points:

The following table describes how these points would be stored in the module:

1300

Words 2600 and 2601 (Double-word address 1300)

500

Words 40 and 41 (Double-word address 20. Must
match the configuration of point 500 in M_ME_NC.)

1301

Words 2602 and 2603 (Double-word address 1301)

501

Words 64 and 65 (Double-word address 32. Must
match the configuration of point 501 in M_ME_NC.)

1302

Words 2620 and 2621 (Double-word address 1310)

502

Word 104 and 105 (Double-word address 52.Must
match the configuration of point 502 in M_ME_NC.)

9.2.5 Data Communication

Group Communication

The Group parameter in the module configuration file controls how each
monitored point is transferred between the PTQ-104S and the client unit. The
Group parameter is described in detail in Group Definition (page 98).