Parameter Default Value

Remarks

Selected Value

t

2

10 seconds

Time-out for acknowledges in case of no data
messages (t

2

< t

1

)

t

3

20 seconds

Time-out for sending test frames in case of a
long idle time

Maximum range of values for configurable time-outs: 1 to 255 seconds, accuracy
1 second. (t1,t2,and t3 only)

Maximum number of outstanding I format APDUs k and latest acknowledge
APDUs (w)

Parameter Default Value Remarks

Selected Value

k

12 APDUs

Maximum difference receive sequence number to
send state variable (Maximum value is 19)

w

8 APDUs

Latest acknowledge after receiving w I format
APDUs

Maximum range of values k: 1 to 32767 (2

15

-1) APDUs, accuracy 1 APDU

Maximum range of values w: 1 to 32767 (2

15

-1) APDUs, accuracy 1 APDU

(Recommendation: w should not exceed two-thirds of k).

Port number

Parameter

Value

Remarks

Port number

2404

In all cases

RFC 2200 suite

RFC 2200 is an official Internet Standard which describes the state of
standardization of protocols used in the Internet as determined by the Internet
Architecture Board (IAB). It offers a broad spectrum of actual standards used in
the Internet. The suitable selection of documents from RFC 2200 defined in this
standard for given projects has to be chosen by the user of this standard.

Ethernet 802.3

Serial X.21 interface

Other selection from RFC 2200: