Iec 60870-5-104 server specifications – ProSoft Technology PTQ-104S User Manual

Page 130

Advertising
background image

Reference

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

12TUser Manual

46TIEC 60870-5-104 Server for Quantum

Database Type

Description

Event Generation Point Size

C_DC_NA

Command dual-point database

N/A

2 bit

C_RC_NA

Command step-point database

N/A

1 byte

C_SE_NA

Command normalized-point database

N/A

1 word

C_SE_NB

Command scaled-point database

N/A

1 word

C_SE_NC

Command short-float point database

N/A

2 words

IEC 60870-5-104 Server Specifications
Operating in the Server mode, the module accepts commands from a Client(s) to
read/write data stored in the module’s internal registers. This data is easily and
continuously transferred between the ProTalk module and the Quantum
processor’s data registers.

The IEC 60870-5-104 Server functionality supported by the module includes:
 The IEC 60870-5-104 communication driver is built in accordance to the

approved IEC specification

 The module functions as a Server on the network supporting data read/write

commands from an IEC 60870-5-104 client on the network

 One TCP server socket
 Supports unsolicited messages, either cyclic or spontaneous (cyclic rate is

configurable)

 Supports clock synchronization commands from client or from the Quantum
 Supports Group interrogation (Global, General 1 to 16, Global Counters,

Counters 1 to 4)

 Event time-stamping configurable by type (None, 24 bit, 56 bit)
 Event queue supports 99 points for each data type
 Optional user defined list of acceptable client host IP addresses
 Configurable Common ASDU address (sector) and Information Object

Address

 An IEC Interoperability Document for the ProTalk is available which fully

documents data types supported by the module