Module Configuration

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

12TUser Manual

46TIEC 60870-5-104 Server for Quantum

Assuming that you have chosen registers 400500 to 400563 as the target for
your Command Function 3 you could enter the following command into the
Backplane Data Exchange section of your configuration file.

The fourth command states:

Field

Value

Meaning

Cmd Type

3

The type of operation to perform
3 = Read/Write special function to the Quantum.

PTQ Address

0

This is ALWAYS 0 and will not overwrite your database.

Point Type

4

The range of registers to read from the Quantum
4 = 4:x style register

Quantum Address

500

The starting address of the data within the Quantum
This would be Point Type + Quantum Address
Example: 40000 + 500 = 40500

Word Count

64

This is ALWAYS 64 words in length.

Note: This command requires two PLC scans to complete. When you issue a Function 3 we will

examine the "Quantum Address" registers, process the information, clear the registers and post the

status if applicable.

Page 60 of 201

ProSoft Technology, Inc.

March 4, 2013