Block format for read, 6 read module's time to processor (9970) – ProSoft Technology PTQ-104S User Manual

Page 72

Advertising
background image

Module Configuration

48TPTQ-104S Rev 1 ♦ 47TQuantum Platform

12TUser Manual

46TIEC 60870-5-104 Server for Quantum

The structure of each event record in the block is shown in the following table.

Word Offset in Event
Record

Data Field(s)

Description

0

DB Index

This is the index for the point in the module's
database. This corresponds to the order of point
definition for the module data types. This is not the
point address for the event. For example, to refer to
the third configured point, enter a value of 2 (first event
is 0).

1

ASDU

This is the ASDU data type for the event message.
Valid entries for this field are as follows:
1=single-point
3=double-point
5=step
9=normalized
11=scaled
15=integrated total

2

Qualifier

This is the qualifier code for the event message. This
parameter is only used for ASDU types 5, 9, 11 and
15. Refer to the IEC Protocol Specification for a full
listing of valid qualifier codes for one of these ASDU
types.

3

Year

This field contains the four-digit year for this event.

4

Month

This field contains the month value for the event. Valid
Values: 1 to 12

5

Day

This field contains the day value for the event. Valid
Values: 1 to 31

6

Hour

This field contains the hour value for the event. Valid
Values: 0 to 23

7

Minute

This field contains the minute value for the event. Valid
Values: 0 to 59

8

Seconds and
Milliseconds

This field contains the seconds and milliseconds value
for the event. Valid Values: 0 to 59,999 (59 seconds
and 999 milliseconds).

9 to 14

Data

These words contain the data for the event. For single-
and double-point, step, and measured value events,
the first word is used. For integrated total events, the
first two words are used.

Block Format for Read

Word Offset in Block Data Field(s)

Description

1

Block ID

This word will contain the value of 9958

5.4.6 Read Module's Time to Processor (9970)

If a value of 9970 is placed in the control register, the processor will read the
module's current time.

Page 72 of 201

ProSoft Technology, Inc.

March 4, 2013