Troubleshooting vt-probes – GE Industrial Solutions CPS6000-M2 User Manual

Page 109

Advertising
background image

CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

109

Troubleshooting VT-Probes

Checking for Defective VT-Probes

(If a Voltage Channel Failure and/or Thermal Probe Failure alarm occurs)

Step

Action

1

Disconnect all probes by disconnecting 1-wire cable at P7 on the controller.

2

Run the command: MENU > CONTROL / OPERATIONS > UNINSTALL
EQUIPMENT.
The controller green normal LED should light

3

Reconnect 1-wire cable at P7 on the controller with only one thermal probe connected.

4

Run the command: MENU > STATUS / MEASUREMENTS > BATTERIES and
scroll down to TEMP PROBES PRESENT It should read one

5

Add the next probe and repeat step 4 to make sure the proper number of probes
appears. (wait at least 1 minute for it to recognize)

6

If a probe is not recognized or an alarm is generated then this probe may be defective.

7

Remove defective probe and repeat step 2 to uninstall that probe.

8

Repeat step 5 until all probes are installed and recognized.