AC Input

• Connects to AC termination

panel at the top of the
system.

• One 1-inch conduit per

shelf.

• Each rectifier fed

individually by 10 gage wire
protected with a 20A circuit
breaker or fuse.

Battery Options and Monitoring Features

Battery Options

• Designed for operation with Flooded, VRLA,

NiCad, and Lithium batteries (Nickel metal
Hydride in the future).

• Half-height systems mount on Unigy II

batteries, Full Height systems may be
equipped with battery trays.

• Battery trays available for up to 170Ahr

batteries with Anderson PowerPole®
connectors or circuit breaker disconnects.


Battery Monitoring Features
• Open String (OS) Alarms
• Emergency Power Off (EPO) for

disconnecting batteries from the system

• Temperature/voltage probes (up to 16) used in

Battery Management options

ƒ

Slope Thermal Compensation

ƒ

Battery High Temp Disconnect

• Battery Discharge Test
• Battery Shunt

Low Voltage Battery Disconnect/Reconnect Contactor (LVBD)