Ac input, Battery options and monitoring features – GE Industrial Solutions CPS6000-M2 User Manual
Page 14
CPS6000-M2 Installation Guide H5694720
Issue 8 January 2008
14
AC Input
• Connects to AC termination
panel at the top of the
system.
• One 1-inch conduit per
shelf.
• Each rectifier fed
individually by 10 gage wire
protected with a 20A circuit
breaker or fuse.
Battery Options and Monitoring Features
Battery Options
• Designed for operation with Flooded, VRLA,
NiCad, and Lithium batteries (Nickel metal
Hydride in the future).
• Half-height systems mount on Unigy II
batteries, Full Height systems may be
equipped with battery trays.
• Battery trays available for up to 170Ahr
batteries with Anderson PowerPole®
connectors or circuit breaker disconnects.
Battery Monitoring Features
• Open String (OS) Alarms
• Emergency Power Off (EPO) for
disconnecting batteries from the system
• Temperature/voltage probes (up to 16) used in
Battery Management options
Slope Thermal Compensation
Battery High Temp Disconnect
• Battery Discharge Test
• Battery Shunt
Low Voltage Battery Disconnect/Reconnect Contactor (LVBD)