CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

35

Installing Batteries

Installing Battery Trays

Optional battery trays are suitable for use with general trade VRLA batteries. VRLA batteries
come in two jar widths; approximately 4.25” width, typically used in 19” frame applications and
approximately 5” width, typically used in 23” frame applications. These battery trays
accommodate both types.

Step

Action

1

Position the battery tray in the frame as
shown. Secure with provided (Comcode
901078717) rack screws.

Installing Tray Mounted Batteries

The system can be configured with battery trays sized for various batteries and may include
optional factory installed battery disconnect or battery mid-string voltage and temperature
monitoring units.

WARNING: All batteries contain hazardous electrical energy. Lead-acid
batteries contain sulfuric acid and explosive hydrogen gas. Follow all precautions
noted in the literature accompanying the batteries. Use only insulated tools.

CAUTION: Equipment frame anchoring, load rating, and seismic zone rating
should be verified before field installing trays and batteries.