Step
Action
3
Place front bracket on battery
tray. Batteries sit on flange of
bracket holding it in place.
Note: For systems with larger
batteries the front bracket is
mounted to extend beyond the
front of the tray.
4
Connect one end of the 2 gage
cable to the input bus of the
disconnect switch. Secure with
1/4-20 hex nuts (901352617)
provided.
Torque to 65 in-lb.
5
Re-attach clear plastic cover to
disconnect switch and secure
with 6-32 screws.
6
Place four batteries on each
battery tray.
Position three Battery Spacers
between the batteries.
7
Interconnect three inter-cell bus
bars to configure one 48V
battery string per the battery
manufacturer’s instructions.