Installing TPL-C Fuse Holders and Panels
TPL-C Fuse holders can either be factory or field installed per kit CC109129129128. The
following figure shows the installation of this kit and corresponding fuse installation. Note that
the fuse snaps into the fuse handle which is then pushed into the holder.
Step
Action
1
Ensure Fuse Holders are empty prior to making any connections.
2
Secure Load Cable connections with provided hardware (per cable):
(2) 841064777 3/8-16 nut
(2) 801829607 3/8-inch lockwasher
(2) 814251898 3/8-inch flat washer
Use 9/16” socket. Torque to 240 in·lbs.
WARNING:
Do not install load fuses until the load equipment is ready to be energized.