CPS6000-M2 Installation Guide H5694720
Issue 8 January 2008
32
Battery or Battery Stand Mounted Half-Height Frames:
Step
Action
1
Place and secure frame to battery or battery stand per instructions provided with the
battery stand or adapter.
Connecting Frame Ground
Select a Frame Ground landing on the top of the frame and clean.
Step
Action
1
Secure Frame Ground connection with
provided hardware:
(2) 801256165 ¼-20 x 3/4" HH bolt
(2) 801829557 ¼-inch lockwasher
(2) 802841577 ¼-inch flat washer
If required by local code or practice,
treat with an oxidation inhibitor such as
NO-OX.
Use 7/16” socket. Torque to 65 in·lbs.
Note: Landings are compatible with lugs
with 5/8” hole spacing for ¼” or 6mm
hardware.