CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

32

Battery or Battery Stand Mounted Half-Height Frames:

Step

Action

1

Place and secure frame to battery or battery stand per instructions provided with the
battery stand or adapter.

Connecting Frame Ground


Select a Frame Ground landing on the top of the frame and clean.

Step

Action

1

Secure Frame Ground connection with
provided hardware:
(2) 801256165 ¼-20 x 3/4" HH bolt
(2) 801829557 ¼-inch lockwasher
(2) 802841577 ¼-inch flat washer

If required by local code or practice,
treat with an oxidation inhibitor such as
NO-OX.

Use 7/16” socket. Torque to 65 in·lbs.

Note: Landings are compatible with lugs

with 5/8” hole spacing for ¼” or 6mm
hardware.