Plant battery test – GE Industrial Solutions CPS6000-M2 User Manual

Page 123

Advertising
background image

CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

123

point and the Lower Thermal Limit (ltt) will result in a proportional increase of plant voltage to a
level corresponding to (lsp*(ntt-ltt)*24)V above the fsp at the ltt.

Upper Temperature Slope (usp): The slope rate for the voltage decrease per cell when the
battery temperature is above the ntt (Battery Thermal Slope Nominal Temperature).

Upper Temperature Limit (utt): The upper temperature where Battery Thermal Compensation
will have reduced plant voltage to a level corresponding to (usp*(utt-ntt)*24)V below the fsp.
Plant voltage will be reduced proportionally at any temperature between this point and the Battery
Thermal Slope Nominal Temperature (ntt).

Battery Thermal Alarm Threshold (thr): A monitored battery temperature above this threshold
results in a Battery Thermal alarm with a PMN severity.

Battery Thermal Step Temperature (spt): A monitored battery temperature above this
threshold results in an additional 4.08V “step” decrease in plant voltage.

Plant Battery Test

The following is a list of plant battery test parameters that can be configured in the controller. The
result of the Plant Battery Test is available in the “Batteries” sub-menu of the “Status” menu.

Manual Test: Permits manually starting a battery discharge test. The test can be set to end on
either of the following two parameters.

Duration: The duration of the test can be set from 0.1 hours to 99.9 hours.

Cutoff Cell V: The test can be set to end when battery cell voltage reaches this cutoff voltage.
Cutoff voltage can be set from 1.5V to 2.0V.

Automatic Test: This utility offers the flexibility of running pre-programmed battery tests at
specific times and days, and for specific durations.

Automatic Test: Enable or disable automatic periodic running of the battery test. The factory
default setting is disabled.

Interval: The test interval (time between tests) can be set from 1 to 18 months in 1 month
increments. The factory default setting is 12 months.

Next Test: Enter a particular day in dd-mm-yy format to automatically run the battery test on that
day.

Start Time: Enter a particular time in hh-mm format to automatically run the battery test at that
time. The setting can be configured from 0 to 23 hours. 00:00 is midnight.

Hours from BD: Time interval needed to elapse since the last Battery on Discharge alarm before
a battery test can be performed. This can be set from 0 to 240 hours in 1 hour increments. The
factory default setting is 72 hours.

Recharge Amp Limit: This section contains the settings for battery recharge current limit.