GE Industrial Solutions CPS6000-M2 User Manual

Page 77

Advertising
background image

CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

77

Step

Configuration

Attribute to Change

Menu Path/Action

the cursor to the field and use the <+> or <-> key to Enable or
Disable. Press <ENTER> to save the change.

High Temp
Comp

This feature allows the system to compensate for high
temperatures.

Volt Step
Down

Battery step temperature can be set from 113-185F. At this
temperature, the system voltage is reduced by 0.17 X # of
cells/string.

High Comp
Limit

This sets the maximum temperature for which thermal
compensation is active.

Decrease

This sets the slope (mV/degC) for high temperature
compensation.

Nominal
Temp

This field set the temperature at which no compensation is
required. The system voltage is at the set-point float mode.

Low Temp Comp

This feature allows the system to compensate for low
temperatures.

Low T Comp

This enables or disables the low temperature compensation
feature.

Low Comp
Limit

This sets the minimum temperature for which thermal
compensation is active.

Increase

This sets the slope (mV/degC) for low temperature
compensation.

Recharge Current
Limit

This feature sets the total amount of current that will be
allowed to recharge the batteries.

Limit

The configuration of this field enables or disables the feature.

8

Limit to

This programmable value sets the maximum amount of
recharge current (in Amps) that will be allowed for recharging
the batteries. The range is from 10 – 1000A.

Contactors

Up to three optional LVD devices can be connected to a
Millennium and configured from this screen.

Contactor 1-3

9

Type

This setting identifies the type of contactor, BATTERY,
LOAD or NONE that has been installed in the plant. Be sure
that the wiring for the contactor being configured matches the