CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

97

Controller

Status Display

Power

Unit

LEDs

Dist.

Module

LED

Possible

Problem(s)

Possible Solution(s)


(one

rectifier)


• Rectifier lost

communicati
on with
controller.

1. Reset the rectifier by

removing the rectifier,
waiting approximately
30 seconds, and
replacing.

2. If problem persists,

replace the rectifier.

3. If problem still persists,

call your local field
representative.

MIN Minor

Communication
Fail

• Rectifier

removed
from a
running
system, but
not
uninstalled.

1. Issue the “uninstall

equipment” under the
operations menu for any
rectifier that was
removed.

MAJ Major

Communication
Fail


• LVD Board

lost
communicati
on with the
controller.

1. Replace Distribution

Module Board.

2. If problem persists, call

your local field
representative.

MIN Clock

Battery Low



• Internal

Lithium
Battery Is
Low

1. The battery is not field

replaceable. The
controller unit must be
replaced.

2. Off-load all desired

information such as
alarm history, statistics,
and any field
configuration that is
different than the
standard.

3. Replace controller, and

upload any non-standard
configuration.