CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

78

Step

Configuration

Attribute to Change

Menu Path/Action

type chosen here. To toggle between the various contactor
types, move the cursor to one of the fields and use the <+> or
<-> key to select the desired type. Press <ENTER> to save the
change.

Disconnect

This setting configures the plant voltage at which the contactor

will disconnect from the bus. Use the <+> or <-> key to adjust

the voltage to the desired level. Press <ENTER> to save the

change.

Reconnect

This setting configures the plant voltage at which the contactor
will reconnect to the bus. To prevent the contactor from re-
operating when battery voltage increases due to load removal,
a voltage several volts higher than the disconnect voltage is
recommended. Use the <+> or <-> key to adjust the voltage to
the desired level. Press <ENTER> to save the change.