GE Industrial Solutions CPS6000-M2 User Manual
Page 78
CPS6000-M2 Installation Guide H5694720
Issue 8 January 2008
78
Step
Configuration
Attribute to Change
Menu Path/Action
type chosen here. To toggle between the various contactor
types, move the cursor to one of the fields and use the <+> or
<-> key to select the desired type. Press <ENTER> to save the
change.
Disconnect
This setting configures the plant voltage at which the contactor
will disconnect from the bus. Use the <+> or <-> key to adjust
the voltage to the desired level. Press <ENTER> to save the
change.
Reconnect
This setting configures the plant voltage at which the contactor
will reconnect to the bus. To prevent the contactor from re-
operating when battery voltage increases due to load removal,
a voltage several volts higher than the disconnect voltage is
recommended. Use the <+> or <-> key to adjust the voltage to
the desired level. Press <ENTER> to save the change.