CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

34

Connecting AC Utility

WARNING: Disconnect all AC branch circuits prior to making AC connections
to the CPS6000 Plant System. When connecting to utility source, ensure
compliance to all local and national wiring rules.

Step

Action

1

• AC is connected to terminal blocks located at the top of the equipment frame.

• Route and attach conduit or other commercial fitting. A 1-inch conduit is required per

rectifier shelf.

2

• Pull and terminate AC wire.

• Terminal blocks are provided for up to twenty rectifiers (four shelves).

• Each rectifier must be fed by 10 gauge wire protected by a 20A circuit breaker or

fuse.


• Terminate ground connection on terminal blocks or optional lugs.