CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

58

Step

Action

2

3

Secure the module connection unit and route the wires through the open-faced
bottom of the connection unit.

4

Make the connections to TB2 on the connection unit:

TB-2 Pin

RPM Conductor

Color

RPM Conductor

Description

IN

Blue or White

Power/Communications

OUT

Blue or White

Power/Communications

SHIELD Bare

wire

Shield

*connections of the bus wire are NOT polarity sensitive.
* there are 2 IN, and 2 OUT connections. Either one may be used.

5

Locate the control unit. This is the half with circuitry on it.

6

Each RPM must have a unique switch address to be recognized by the controller. In
the lower right hand side of the control unit (inside), are two rotary switches. Set
SW-1 (LO) to 1. The module will be recognized as 01 by the controller. Other
modules added cannot have the same address or 00 for the address.

7

Carefully attach the control unit to the connection unit using the ribbon connector.

Note

This connector/cable is not keyed, so be careful to line up the pins properly.

8

After approximately 1 minute, the green LED on the front of the module will blink
once approximately every 5 seconds.