GE Industrial Solutions CPS6000-M2 User Manual

Page 96

Advertising
background image

CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

96

Controller

Status Display

Power

Unit

LEDs

Dist.

Module

LED

Possible

Problem(s)

Possible Solution(s)

MIN Battery High

Temperature



• Batteries have

exceeded
temperature
threshold set
by user.

1. Call your local field

representative.

MIN Thermal

Probe Fail



Battery thermal

probe failed

.

1. Ensure thermal probe is

properly connected to
thermal probe cable.

2. Ensure cable is properly

connected to the rear of
the Distribution Module.

3. If problem persists,

replace thermal probe.

4. If problem still persists,

call your local field
representative.

No response

• Controller

failure, all
devices on
the
communicati
on bus
reporting loss
of
communicati
on with
controller.

1. Check controller to

ensure it is properly
inserted into its slot. If
so, perform the
following steps:

2. Remove the controller

board for 1 minute and
then reset.

3. If problem persists,

replace controller with
new controller board.

4. If problem still persists,

call your local field
representative.