GE Industrial Solutions CPS6000-M2 User Manual
Page 96
CPS6000-M2 Installation Guide H5694720
Issue 8 January 2008
96
Controller
Status Display
Power
Unit
LEDs
Dist.
Module
LED
Possible
Problem(s)
Possible Solution(s)
MIN Battery High
Temperature
• Batteries have
exceeded
temperature
threshold set
by user.
1. Call your local field
representative.
MIN Thermal
Probe Fail
•
Battery thermal
probe failed
.
1. Ensure thermal probe is
properly connected to
thermal probe cable.
2. Ensure cable is properly
connected to the rear of
the Distribution Module.
3. If problem persists,
replace thermal probe.
4. If problem still persists,
call your local field
representative.
No response
• Controller
failure, all
devices on
the
communicati
on bus
reporting loss
of
communicati
on with
controller.
1. Check controller to
ensure it is properly
inserted into its slot. If
so, perform the
following steps:
2. Remove the controller
board for 1 minute and
then reset.
3. If problem persists,
replace controller with
new controller board.
4. If problem still persists,
call your local field
representative.