GE Industrial Solutions CPS6000-M2 User Manual

Page 81

Advertising
background image

CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

81

Voltage Threshold Ranges and Default Values

The following table provides the ranges and factory default settings of key configurable voltage
thresholds in the Millennium II.

Voltage Threshold Ranges and Default Values

Low

High

Default

Very Low Voltage (VLV)

24V

20.00 25.50 23.00

48V

40.00 51.00 46.00

Battery on Discharge (BD)

24V

Float

23.00 28.00 25.00

24V

Boost

23.00 28.00 25.00

48V

Float

46.00 55.00 51.00

48V

Boost

46.00 55.00 51.00

High Float Voltage (HFV)

24V

Float

24.75 29.75 26.50

24V

Boost

25.75 31.75 26.50

48V

Float

50.00 60.00 53.00

48V

Boost

52.00 60.00 53.00

High Voltage Shutdown Alarm (HV)

24V

Float

24.75 29.75 26.8

24V

Boost

25.75 31.75 26.8

48V

Float

50.00 60.00 53.6

48V

Boost

52.00 60.00 53.6

Rectifier On Threshold (ROT)

24V

20.00 25.00 22.00

48V

40.00 51.00 44.00

Controller Alarm Severity, LED and Relay Default Values

The following tables provide the various controller alarms and their associated default severity
and LED assignments as well as rectifier specific alarms. These items may be reconfigured
through remote means.

Controller Alarm Severity, LED and Relay Default Values

Symbol

Default Designation

Default

Severity

Default LED Default Relay

AAC

ACO Active

RO

None

None

ABS

Alarm Battery Supply Fuse

Major

CTLR

CTLR

AMJ

Auxiliary Major

Major

None

None

AMN

Auxiliary Minor

Minor

None

None

ATA

Alarm Test Active

RO

None

None