CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

57

Remote Peripheral Monitoring (RPM)


Monitoring modules available consist of:

• 221F -50-150mV Shunt monitors (6 channels + 1 temperature channel)
• 221J 0-100mV DC Voltage transducer monitors (6 channels + 1 temperature channel)
• 221A 0-3V DC Voltage monitors (6 channels + 1 temperature channel)

• 221B 0-16V DC Voltage monitors (6 channels + 1 temperature channel)
• 221C 0-70V DC Voltage monitors (6 channels + 1 temperature channel)
• 221D 0-200V DC Voltage monitors (6 channels + 1 temperature channel)
• 222A Binary Input monitor (6 channels + 1 temperature channel)
• 223T Temperature monitor (7 Channels)
• 214A Control Relay module (3 sets of programmable form C relay outputs)


The user may connect a maximum of 95 of any combination of these modules serially.

Step

Action

NOTE:

This section only describes a single module connection to the controller. Modules
MUST BE PROGRAMMED after they have been installed or they may not function
properly. Detailed connection and configuration information may be found in the
RPM Product Manual 167-790-063.

1

Using RPM bus cable (comcode 407377704), wrap the cable through the EMI
inductor bead twice. Place the bead approximately 3 inches from the controller.
Connect the bus cable to TB-1 on Millennium and TB101 on the RPM

TB-1 Pin

Assignments

TB-1 Pin

Descriptions

RPM

Conductor

Color

RPM Conductor

Description

6

*6

Blue or White

Power/Communications

8

*8

Blue or White

Power/Communications

9 or 10

FGND

Bare wire

Shield


*connections of the bus wire are NOT polarity sensitive.