7 troubleshooting – GE Industrial Solutions CPS6000-M2 User Manual

Page 92

Advertising
background image

CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

92

7 Troubleshooting

Controller

Status Display

Power

Unit

LEDs

Dist.

Module

LED

Possible

Problem(s)

Possible Solution(s)

No Alarms

Normal Operation

(one

rectifier)

• Single

rectifier not
receiving ac
power.

• AC input

circuit
breaker has
opened.

• AC input

voltage is
out of range.

1. Verify rectifier input

circuit breaker is closed.

2. Verify ac power to

rectifier is available and
in range.

3. If problem not corrected,

replace rectifier.

MIN AC Fail

• A rectifier has

been
removed
from the
system
while it is
unpowered.

1. Issue the “uninstall

equipment” under the
operations menu for any
rectifier that was
removed while
unpowered.