Installing Optional Circuit Packs

Field-Installable Circuit Packs

BSM5 Modem Card

Step

Action

Note Installation or replacement of this pack can be done “hot”; power removal is not

necessary.

1

Remove the controller plastic front cover.

2

Place insulator under BSM5 modem and install to the door using four 407882141
standoffs. Wrap insulator around modem and secure with four 845143866 screws.

3

Connect 848091798 cable assembly between the BSM5 J100 plug and P201 on the
MCR1 board.

4

Note: This step may be performed at a later time

Connect a telephone cable to the RJ11 connector at the top of the BSM5 board
OR
Connect Tip/Ring conductors to TB1 at the top of the board.
NOTE: Tip is TB1 pin 1 (Pin closest to the RJ11 connector) and Ring is Pin 3. Pin 2
is not used.

5

Operate the controller reset switch on the MCR1 board in the lower left corner of the
MCR1 board.

Note The Password Reset button is to the LEFT of the serial port connector (Not present on

the MCR1B must use the front panel), and the Controller Reset is to the right of the
serial connector.