Anchoring Frame

Floor Mounted Frames

Using the 847135688 Floor Anchor Kit (recommended):

Anchor Type (Hilti)

Wrench

Hole Size

Torque

(4) 12 mm Cap Bolts

19 mm

18mm
100mm deep

720 in·lbs
60 ft·lbs
81.6 N·m

Note: For systems with tray mounted batteries at sites requiring Seismic Zone 4 rating, (2)

847135688 kits are required to provide (8) floor anchors.

Note: If using Equivalent Floor Anchors, make sure the floor anchors are rated for this
application.

Step

Action

1

Mark floor anchor locations, using the provided Floor Template.

G103 7ft Standard Frames

G104 7ft Heavy Duty Frames

2

Drill anchor holes.
Caution: Follow safe floor drilling procedures to prevent possible asbestos exposure.

3

Place frame and install floor anchors according to manufacturer requirements.