Anchoring Frame
Floor Mounted Frames
Using the 847135688 Floor Anchor Kit (recommended):
Anchor Type (Hilti)
Wrench
Hole Size
Torque
(4) 12 mm Cap Bolts
19 mm
18mm
100mm deep
720 in·lbs
60 ft·lbs
81.6 N·m
Note: For systems with tray mounted batteries at sites requiring Seismic Zone 4 rating, (2)
847135688 kits are required to provide (8) floor anchors.
Note: If using Equivalent Floor Anchors, make sure the floor anchors are rated for this
application.
Step
Action
1
Mark floor anchor locations, using the provided Floor Template.
G103 7ft Standard Frames
G104 7ft Heavy Duty Frames
2
Drill anchor holes.
Caution: Follow safe floor drilling procedures to prevent possible asbestos exposure.
3