GE Industrial Solutions CPS6000-M2 User Manual

Page 98

Advertising
background image

CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

98

Controller

Status Display

Power

Unit

LEDs

Dist.

Module

LED

Possible

Problem(s)

Possible Solution(s)

No Alarm, but
individual
Shunt Currents
are displayed at
or above their
maximum
display values
(≥600A for
loads, ≥800A for
battery)









• One or both of

the QS871A
shunt inputs
is open-
circuit.

1. Verify that the

respective shunt has its
green and yellow wire
connections attached
used for the current
measurements.

2. Verify the shunt

connection to the
QS871A is good by
verifying the green and
yellow wire connections
from the shunt follows
through to the 10-pin
connector at the
respective QS871A.

Advertising