CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

29

Wiring Guidelines
• All electrical connections should be made using the proper crimping tools and dies and

should be torqued to values specified.

• All building wiring should comply with the NEC and other applicable local codes.
• The temperature rating of the wire must be 90°C minimum.. Wire gauge must be sized based

on 75°C wire and the ampacity of the associated branch-circuit protection.

• Wiring internal to enclosed equipment cabinets must be rated no less than 105° Celsius.
Packaging
• All packages should be opened with a box cutter with the blade minimally exposed so that

only the sealing tape is cut.

• Save all packaging material until the system has been powered up and all parts are operating

within specifications.

Installation Tools

You will need the following tools to install and test the CPS6000-M2 System.

• Wire cutters and strippers
• Heat shrink gun
• 5/16-inch (8 mm) hex driver
• Digital meter with an accuracy of

±0.02%

• Screw drivers (flat-blade and Phillips)
• ESD wrist strap
• 48V test load
• Calibrated clamp-on dc current meter

(0.1 ADC sensitivity)

• Torque wrench
• Socket wrenches:

− 7/16” and 9/16” for load and

battery connections;

− 19 mm for anchor bolts;
− 12" extension for socket

• Masonry drill kit as required
• Compression for installation of various

compression lugs

• Protective canvas
• Insulating rubber mat
• Standard insulated installation tools,

screwdrivers, etc.

• Windows-based personal computer

laptop (PC) and cable to connect the PC
communications port to the local port of
the controller OR a CAT5 LAN cable.