CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

93

Controller

Status Display

Power

Unit

LEDs

Dist.

Module

LED

Possible

Problem(s)

Possible Solution(s)



(multiple

rectifiers)



• Multiple

rectifiers not
receiving ac
power.

• AC input

circuit
breakers have
opened.

AC input

voltage is out
of range

.

1. Verify rectifier input

circuit breakers are
closed.

2. Verify ac power to

rectifiers is available and
in range.

3. If problem not corrected,

replace rectifiers.

MIN AC Fail,
MAJ Multiple AC

Fail

• One or more

rectifiers
have been
removed
from the
system while
it is
unpowered.

1. Issue the “uninstall

equipment” under the
operations menu for any
rectifier that was
removed while
unpowered.

MAJ Battery on

Discharge



• Rectifier output

voltage has
fallen below
the battery on
discharge
threshold set
by the user.

1. Investigate other alarms

that may be present such
as rectifier related
problems.

2. If ac power is present

but the system voltage
remains low, call your
local field representative