CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

95

Controller

Status Display

Power

Unit

LEDs

Dist.

Module

LED

Possible

Problem(s)

Possible Solution(s)

(all

rectifiers)

• All rectifier

outputs have
dropped
below 18V
(36V), all
rectifiers
have shut
down*.

Defective

controller.

1. Remove controller and

reset the rectifiers by
removing the rectifiers,
waiting approximately
30 seconds, and
replacing the rectifiers.

2. If output voltage does

not go to set-point
previously set by user,
call your local field
representative.

MAJ High Voltage

(one or

multiple

rectifiers)

• High output

voltage from
rectifier(s)

• Rectifier(s)

high voltage
shut down

∗.

Internal

rectifier(s)
failure

1. Reset the rectifier(s) by

removing the rectifier(s),
waiting approximately
30s and replacing the
rectifier(s).

2. If problem persists,

replace rectifier(s).

3. If problem still persists,

call your local field
representative.

MAJ Fuse Major

• One or more

output circuit
breakers or
fuses have
opened.

1. Clear circuit fault(s).
2. Reset circuit breaker(s)

or replace fuse(s).

MAJ Contactor

Open


• One or more

LVD
contactors is
manually
forced open.

1. Place disconnect

switch(s) in ON
position.