GE Industrial Solutions CPS6000-M2 User Manual

Page 111

Advertising
background image

CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

111

System Configuration Table

H5694720

Group

Description Rack

Spaces

Frameworks

102

42 inch tall framework

22U

103

7 foot tall light-duty framework (600 lb zone 4, 1200 lb zone 2)

46U

104

7 foot tall heavy-duty framework (1200 lb zone 4, 1800 lb zone 2)

46U

Battery Tray e/w Anderson Disconnects and 2 Gauge Cable

440

Battery Tray on 7U (12.25”) spacing for 100AH Batteries

7U

450

Battery Tray on 8U (14.00”) spacing for 110-150AH Batteries

8U

470

Battery Tray on 9U (15.75”) spacing for 170AH Batteries

9U

Battery Tray e/w Disconnect Breaker Panel and 2 Gauge Cable

441

Battery Tray on 7U (12.25”) spacing for 100AH Batteries

7U

451

Battery Tray on 8U (14.00”) spacing for 110-150AH Batteries

8U

471

Battery Tray on 9U (15.75”) spacing for 170AH Batteries

9U

Rectifier Shelves with AC Termination Panel

255

Two 5-position Rectifier Shelves, AC Termination Panel and space
for one Group 660 or 661 Distribution Panel

17U

256

Four 5-position Rectifier Shelves, AC Termination Panel and space
for one Group 660 or 661 Distribution Panel

22U

Distribution

660

Distribution Panel e/w Millennium II controller. Distribution
includes 38 positions for bullet style Fuse Holders or Breakers, and 8
positions for equipping Group 600_ Breakers, Fuses or Contactors.

--

661

Distribution Panel e/w Millennium II controller. Distribution
includes 19 positions for bullet-style Fuse Holders or Breakers, 4
TPL-B 0-250A Fuse Holders with Load Shunts, 4 TPS 0-70A Fuse
Holders with Load Shunts, and 8 positions for Group 600_ Breakers,
Fuses or Contactors. (Includes shunt module RPM for monitoring up
to 12 shunts on TPS, TPL-B and TPL-C Fuse Holders)

--

The Following Groups ordered for Group 660 or 661

(8 positions Available)

600B

150A KS22012 Circuit Breaker Kit.
(Breaker e/w 25mV shunt and wiring to connect to RPM)

1-pos

600E

250A KS22012 Circuit Breaker Kit.
(Breaker e/w 25mV shunt and wiring to connect to RPM)

1-pos

600G

400A KS22012 Circuit Breaker Kit.
(Breaker e/w 25mV shunt and wiring to connect to RPM)

2-pos

600M

TPL-C Fuse Holder and 1500A, 50mV load shunt
Kit includes wireset for connecting to shunt RPM

2-pos

600R

6 channel shunt module (RPM) for monitoring shunts on Groups
600B, 600E, 600G and 600M in a Group 660 Panel.
(661 already provides two RPMs). (Mounts on distribution door)

no-pos

600T

800A Low Voltage Battery Disconnect (LVBD) Contactor.

3-pos

Advertising