BSL Alarm and Control Inputs

Alarm

Pin

Number

Signal Name

61 LVD2

Low Voltage 2 Disconnect State Detect

62 LVD2R

Fuse Alarm Major

63

FAJ

Fuse Alarm Minor

65

FAN

Auxiliary Alarm Major

64

AMJ

Auxiliary Alarm Minor

66 AMN

Timer Float Control

67

TFLT

Timer Boost Control

68

TBST

Timer Control Return

69

TRTN

70 PBTR

Plant Battery Test

71 PBT

Open String Detect

72

OS

Transfer Rectifier 1

73

TR1

General Purpose Input 4

74

IN-4 (previously TEQ)

General Purpose Input -5 (Previously
Engine Transfer)

75

IN-5 (Previously ETR)

77 RO

Reserve Operation

78 ROR

Transfer Rectifier 2

79

TR2

Transfer Rectifier 4

80

TR4

Reserve Battery-Emergency Power Off

81

RBRPO

General Purpose Input 1

82

IN-1

BTP or General Purpose Input 2

83

IN-2/BTP

Low Voltage 1 Disconnect State Detect

84

LVD1

Transfer Rectifier 3

85

TR3

General Purpose 4-20mA Measuring
Circuit

87 4-20mA

General Purpose 4-20mA Measuring
Circuit-RTN

88 4-20mAR

BTPFLT or Generic Input 3

89

IN-3/ BTPFLT

Low Voltage 3 Disconnect State Detect
Also Battery Thermal Protect Major

90 LVD3/

BTMJ

General Purpose 0-5Vdc Measuring
Circuit

91 0-5V

General Purpose 0-5Vdc Measuring
Circuit-RTN

92 0-5VR