CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

79

Controller Defaults

Dip Switch Settings

The Millennium II has 8 dip switch (SW202) positions that may be configured. SW202 is located
on the MCR1 board, above the MCR2 board.

Millennium II Controller Dip Switch Settings

Switch

Position

Default

Description

Closed

(1)

Open

(0)

SW202-8

1

Front Panel Configuration

ENABLED

DISABLED

SW202-7

1 Modem/Aux/Local/Network/

Port

Setting Configuration
(Remote Access)

ENABLED DISABLED

SW202-6

0

Enhanced Security Mode (See Table
5-I, for features affected

ENABLED DISABLED

SW202-5

1

Auxiliary Port Configuration

RS-232

RS-485

SW202-4

0

Remote Rectifier in Standby

ENABLED

DISABLED

SW202-3

0 Boost

Mode

ENABLED

DISABLED

SW202-2

1

Reserved for Future Use

ENABLED

DISABLED

SW202-1

1

Reserved for Future Use

ENABLED

DISABLED

Modem/Aux/Local/Network/ Port Setting Configuration (Remote Access)
The modem and auxiliary ports can be configured for full access or read-only access by properly
configuring DIP switch 202-7. Full access with Read/Write capability is achieved by closing
SW202-7 (Set to a “1”).

Enhanced Security Mode
Restricted access is also available. When Enabled, the controller prevents remote configuration
changes via the modem, network, and auxiliary ports that will affect the state of the plant, even
when logged in as a Super-User or Administrator. This enhanced remote security is enabled and
disabled with DIP switch SW202-6. The functions and parameters restricted with the enhanced
remote security feature are listed below.