GE Industrial Solutions CPS6000-M2 User Manual

Page 113

Advertising
background image

CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

113

Battery Monitoring Equipment

Part #

Description

108987611

QS873A Thermal Probe

CC848817024

10 ft wireset (thermal probe to controller)

848719803

5 ft wireset (thermal probe to thermal probe)

848719811

10 ft wireset (thermal probe to thermal probe)

848652947

10 ft wireset (extend cc848817024 thermal probe cable)

555052-1

In-line coupler (extending thermal probe cable)

Anchors & Frame Ground

Part #

Description

847135688

(4) 12mm Cap Bolt Floor Anchor

848398566

32 ft long green 2 gage cable for H-tap or C-tap to aisle ground ring

848722203

4 ft long green 1/0 gage cable for H-tap or C-tap to aisle ground
ring




Bullet Style Battery Circuit Breakers
Yellow Handle (Alarms on Mid-Trip and in Off position)

Part #

Amperage

CB Positions

Min Wire Ga

CC408574370 50

1

8

408560123 60

1

6

CC408574387 70

1

6

CC408574395 100

1

2

CC408574404 125

2

2

CC408574412 150

2

1/0

CC408574420 200

2

2/0