CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

66

Millennium II Controller Status and Alarms

Alarm Status LEDs

Status

Function

Condition

Normal

Normal operation, no alarms, inputs and outputs are in
their normal range.

Critical Alarm Power to load equipment is at immediate and high risk.
Major Alarm

Power to load equipment is at immediate risk.

Minor Alarm

A problem requiring attention exists, but power to load
equipment is not at immediate risk.

Battery on
Discharge

Batteries are discharging and delivering current to the
load.

Remote
Access
[LAN/Modem]

Blinks to indicate traffic on an attached LAN or
Modem.

Note: Which conditions are indicated as Critical, Major, and Minor Alarms may be configured by
the user.

Equipment Status LEDs

Status

Function

Condition

AC System

AC input to one or more rectifiers is out of range.

Battery

The batteries are not in a normal operating state.

Controller

The system controller has detected an internal
problem.

Rectifier/Converter

A rectifier or converter power unit in the system has
failed

Distribution

The output distribution is not in a normal operating
state.

Remote Modules

There is a problem with a Remote Peripheral
Module (RPM)

Remote Access
[LAN/Modem]

Blinks to indicate traffic on an attached LAN or
Modem.

Audible Alarm

The controller assembly is equipped with a user configurable alarm
buzzer.

Voltage Test Jacks

Voltage Test Jacks allow you to measure the main plant output voltage
with a hand-held meter.