Battery On Discharge Alarms

Step

Action

1

Change BD alarm to 2 volts below float voltage (MENU > CONFIGURATION >
FLOAT SETTINGS > VOLTAGE ALARMS > BD).

2

Adjust the load to 50 amperes.

3

Verify the BD alarm occurs when the system voltage decreases to BD threshold.

4

Verify the BD alarm clears once the voltage has exceeded 0.5V above the BD alarm
threshold.

5

Restore the BD alarm threshold to its previous setting.

High Voltage Alarms

Step

Action

1

Confirm the HV alarm threshold (MENU > CONFIGURATION > VOLTAGE
ALARMS > FLOAT VOLTAGE ALARMS).

2

Adjust the float voltage to a value greater than this threshold (MENU >
CONFIGURATION > FLOAT SETTINGS > SET POINT).

3

Verify an HV alarm is reported by the controller.

4

Restore the float voltage back to its original setting.

5

Restore the HV setting back to its original setting.

6

Verify the alarms clear and the controller returns to Normal.

Manual Contactor Control and Alarms

Step

Action

1

Open the contactor by controller command (MENU > CONTROL / OPERATIONS
> DISCONNECTS).

2

Verify the controller reports a Contactor Open alarm.

3

Close the contactor by controller command.

4

Verify the alarms clear and the controller returns to Normal.

Automatic Contactor Control and Alarms

WARNING: If this is an operating plant with loads, skip this test.

Step

Action

1

Check the disconnect thresholds (MENU > CONTROL / OPERATIONS >
DISCONNECTS).

2

Adjust the float voltage to a value less than this threshold (MENU >
CONFIGURATION > FLOAT SETTINGS > SET POINT).

3

Disconnect the batteries in the plant.

4

Verify the battery disconnect opens and the controller reports a Contactor Open alarm.

5

Restore the plant voltage back to its original setting.

6

Verify the contactor closes.

5

Verify the alarms clear and the controller returns to Normal.