GE Industrial Solutions CPS6000-M2 User Manual

Page 20

Advertising
background image

CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

20

Ringers

Item

Specification

Input Voltage

-40 to -57 Vdc See Output VA Thermal Limiting.

Nominal Input Voltage

-48 Vdc

Input Current

5 A max.

Output
Voltage

ac Component

65 to 100 Vac
Factory Default: 100Vac

ac tolerance

± 5 Vac

Regulation

±5% ac component only

dc Offset

Type of ringing
Battery Backed
Ground Backed
Ground Backed no-dc

-40 to +57 Vdc

Battery Backed

+40 to +57 Vdc

Ground Backed

0 Vdc

Offset Disabled

dc Offset tracks dc Input Voltage

Factory Default: Enabled

Battery or Ground Backed is selected by Ringer
Chassis jumper J12 or by external connection of Ring
Rtn to Battery or to Ground. Factory Default: Battery
Backed by Jumper

dc Offset Tracking
Error

± 3 Vdc

Harmonic Distortion

5% THD

Crest Factor

1.21 to 1.51

Output Frequency

15 to 50 Hz
Factory Default: 20 Hz

Frequency tolerance

± 1 Hz

Output
VA

100

VA

Thermal Limiting

Output VA may be reduced by reducing Vac when
operating simultaneously above 50°C and less than
-50Vdc input.
Vac is reduced only sufficiently to prevent damage to the
ringer.

Load Power Factor

Operating: 0.5 Leading to 0.9 Lagging
No Damage: 0 Leading to 0.7 Lagging

Operating Temperature

-40 to +75 °C See Output VA Thermal Limiting.

Heat Dissipation

50 W (170 BTU / hr)

Under Voltage Shutdown

50% of Output Vac Set Point
While shutdown due to external fault, restart will be
performed at approximately 2 minute intervals.