GE Industrial Solutions CPS6000-M2 User Manual

Page 18

Advertising
background image

CPS6000-M2 Installation Guide H5694720

Issue 8 January 2008

18

Millennium II Controller

General

Specifications

Input Voltage Range

-48 Vdc (Range: 18-60V)

Maximum Input Power

36W depending upon options

Display

Graphic displayed arranged to
8-line by 40-character backlit LCD

Configuration Method

Through front panel LCD display and menu keys
Through IBM compatible PC with RS-232 port
Through LAN internet connection

Mounting Requirements

Door mounted

Input/Outputs

Specifications

Form C Alarm Output Contact Ratings

60VDC at 0.5A

Plant Voltage Measurement

Accuracy

0 to 50 °C (±.05% of full scale + 1

count)

-40 to 85 °C (±0.1% of full scale + 1
count)

Resolution



48V Systems: ±40 mV
48V Systems: ±70 mV
0.01V

Plant Current Measurement

Accuracy

Resolution


0 to +50 °C : ±0.5% of full scale
-40 to +85 °C: ±1.25% of full scale
1A

Temperature Measurement

Accuracy

Thermistor temperature

One-Wire Serial probes


Resolution



-5 to +55 °C: ±2°C
-40 to +85 °C: ±3°C
-5 to +55 °C: ±1°C
-40 to +85 °C: ±3°C
0.1°C

4-20mA Input Monitor

Accuracy
Resolution


±100µA
±10.0µA

General (0-5V) Input

Accuracy

Resolution


0 to +50 °C: ±0.5% of full scale
-40 to +85 °C: ±1.0% of full scale
0.01VDC