background image

Electrical installation − HighLine/StateLine version

Communication
PROFINET® / EtherNet/IP™

6

l

100

EDS84DPS424 EN 5.0

6.7.1

PROFINET® / EtherNet/IP™

Push−pull plug

X31 − fieldbus input, X32 fieldbus output

Pin

Signal

Description

Data

AIDA standard, type RJ45, socket, 8−pole

84DWTX0311

1

Tx+

Transmit path + (transmit)

2

Tx−

Transmit path − (transmit)

3

Rx+

Receive path + (receive)

4

res.

5

res.

6

Rx−

Receive path − (receive)

7

res.

8

res.

M12 plug, 4−pole

X3x − communication

Pin

Signal

Description

Data

Type M12, 4−pole, D−coded
X31 −> sockets
X32 −> sockets

84DPSO05_5

1

Tx+

Transmit path +

2

Rx+

Receive path +

3

Tx−

Transmit path −

4

Rx−

Receive path −

6.7.2

PROFIBUS®

X3x − communication

Pin

Signal

Description

Data

Type M12, 5−pole, B−coded
X31 −> input −> pins
X32 −> output −> sockets

84DPSO05_5

1

P5V2

l

Only assigned at the output

5 V DC / 30 mA (bus termination)

2

RxD/TxD−N

Data line A (received/transmitted data, minus)

3

M5V2

Data ground (ground to 5 V)

4

RxD/TxD−P

Data line B (received/transmitted data, plus)

5

n. c.

− (shield connection above the housing)

The station address can be set via DIP switches 1 ... 64 behind the service hatch.