Diagnostics

Display of operating data, diagnostics

Extensions in EMS version

10

l

161

EDS84DPS424 EN 5.0

10.1.2

Extensions in EMS version

Pos.

Colour

Status

Description

BUS−RDY

green

blinking

Communication has been established

on

Communication has been stopped

off

Communication is not initialised

BUS−ERR

red

blinking fast

Communication error
For PROFINET: Node not recognised

blinking

For PROFINET: Node recognition

on

Communication error

LED1

yellow

Signalling controlled by the PLC program with adjustable
blinking speed

LED2

LED3
(PLC−RDY)

green

flashes

PLC program is not available

blinking fast

PLC program is loaded/saved or parameters are saved

blinking

PLC program is started

on

PLC program is stopped

off

PLC status is undefined / device is switched off

PLC−ERR

red

flashes 3x

Internal system error

flashes 2x

Parameter version or checksum invalid

flashes

Retain memory error

blinking fast

PLC program is stopped by watchdog monitoring

blinking

Error

off

No error / device switched off

Half wave

Half wave coded

DECA

LED4
(PLC−Com)

yellow

flashes 3x

Control bar: full
wave

flashes 2x

Control bar:
negative half
wave

Pre operational

flashes

Control bar:
positive half wave

Silent mode

blinking fast

Command received

Operational

blinking

Error

Error

Error

on

Warning

off

Control bar: no half wave

Not activated