Analog inputs, Synchronous serial interface (ssi), Remote control (irrc) – Lenze 8400 protec Manual User Manual

Page 66: Technical data

Advertising
background image

Technical data

Control terminals
Analog inputs

4

l

66

EDS84DPS424 EN 5.0

4.7.3

Analog inputs

X50

Pin / Name

Feature

Rated value

4 / AU
3 / GA

Voltage input

0.3 ... 10 V
(V < 0.3 V

¢

"0")

Input resistance

> 80 k

W

Sampling frequency

1 kHz (1 ms)

Accuracy

± 0.1 V

Electric strength of external voltage

± 15 V

A/D converter

Resolution 10 bits + sign
Error: 1 digit

º 0.1 %, based on the final value

2 / AI
3 / GA

Current input, parameterisable

0.6 ... +20 mA (I < 0.6mA

¢

"0")

4 ... +20 mA, fail−safe

Input resistance

220

W

Input current in case of open circuit

Display "0" (I < 0.6 mA)

Sampling frequency

1 kHz (1 ms)

Accuracy

± 0.2 mA

Electric strength of external voltage

± 15 V

A/D converter

10 bit resolution
Error: 1 digit

º 0.1 %, based on the final value

1 / 24O
3 / GIO

24 V supply of the external sensors or
potential−free contacts

External supply at 24E: Voltage drop < 2.5 V

Total current for X4x, X50/X8x

1 A

4.7.4

Synchronous serial interface (SSI)

X80

Pin / Name

Feature

Rated value

1 / CLK+

Pos. clock signal

Bit rate: 100 .... 1000 kbits
Data word width: 1 ... 32 bits (effective)
Code: Gray an binary

2 / CLK−

Neg. clock signal

3 / Data+

Pos. data line

4 / Data−

Neg. data line

5 / n. c.

Not assigned

6 / n. c.

Not assigned

8 / 24O
7 / GIO

24 V supply of the external SSI encoders

External supply at 24E: Voltage drop < 2.5 V

Total current for X4x, X50/X8x

1 A

4.7.5

Remote control (IrRC)

IrRC (Infrared Remote Control)

Pin / Name

Features

Rated value

Reach

~5 m

Angle of incidence

~30 °

Advertising