Control cables – Lenze 8400 protec Manual User Manual

Page 82

Advertising
background image

Electrical installation − HighLine/StateLine version

Installation according to EMC (installation of a CE−typical drive system)
Control cables

6

l

82

EDS84DPS424 EN 5.0

6.4.3

Control cables

ƒ

Control cables must be shielded to minimise interference injections.

ƒ

For lengths of 200 mm and more, use only shielded cables for analog and digital
inputs and outputs. Under 200 mm, unshielded but twisted cables may be used.

ƒ

Connect the shield correctly:
– The shield connections of the control cables must be at a distance of at least 50

mm from the shield connections of the motor cables and DC cables.

– Connect the shield of digital input and output cables at both ends.
– Connect the shield of analog input and output cables at one end (at the drive

controller).

ƒ

To achieve an optimum shielding effect (in case of very long cables, with high
interference) one shield end of analog input and output cables can be connected to
PE potential via a capacitor (e.g. 10 nF/250 V) (see sketch).

9300vec043

Fig. 6−2

Shielding of long, analog control cables