Technical data

Rated data

Overview

4

l

47

EDS84DPS424 EN 5.0

Output data

Voltage

Frequency

Rated current [A]

Number of

phases

[V]

[Hz]

up to +45 °C



up to +55 °C



E84Dxxxx7514

0 ... 400/500

0 ... 1000

2.4/1.9

1.8/1.4

3

E84Dxxxx1524

0 ... 400/500

0 ... 1000

3.9/3.1

2.9/2.3

3

E84Dxxxx3024

0 ... 400/500

0 ... 1000

7.3/5.8

5.5/4.4

3

E84Dxxxx4024

0 ... 400/500

0 ... 1000

9.5/7.6

7.1/5.7

3

E84DHxxx7524

0 ... 400/500

0 ... 1000

16.0/12.8

12.0/9.6

3

 Ambient temperature during operation

Power losses

Power loss P

V

[W]

Type

when operating with rated output current I

arated

when controller is inhibited

E84Dxxxx7514

66

27

E84Dxxxx1524

84

E84Dxxxx3024

127

E84Dxxxx4024

155

E84DHxxx7524

232