Detecting and eliminating emc interferences, Electrical installation − ems version – Lenze 8400 protec Manual User Manual

Page 117

Advertising
background image

Electrical installation − EMS version

Installation according to EMC (installation of a CE−typical drive system)

Detecting and eliminating EMC interferences

7

l

117

EDS84DPS424 EN 5.0

7.4.5

Detecting and eliminating EMC interferences

Fault

Cause

Remedy

Interferences of analog
setpoints of your own or
other devices and
measuring systems

Unshielded motor cable

Use shielded motor cable

Shield contact is not extensive enough

Carry out optimal shielding as specified

Shield of the motor cable is interrupted
by terminal strips, switched, etc.

l

Separate components from other
component part with a minimum
distance of 100 mm

l

Use motor choke/motor filter

Install additional unshielded cables
inside the motor cable (e.g. for motor
temperature monitoring)

Install and shield additional cables
separately

Too long and unshielded cable ends of
the motor cable

Shorten unshielded cable ends to
maximally 40 mm